Hydrogen, Carbon Monoxide, and Smoke-and-Heat Composite Fire Detection System for Energy Storage Power Stations
+
  • Hydrogen, Carbon Monoxide, and Smoke-and-Heat Composite Fire Detection System for Energy Storage Power Stations

Hydrogen, Carbon Monoxide, and Smoke-and-Heat Composite Fire Detection System for Energy Storage Power Stations

Keywords:

Hydrogen, Carbon Monoxide, and Smoke-and-Heat Composite Fire Detection System for Energy Storage Power Stations

Product accessories:

Detailed Introduction

 

1. High-sensitivity sensors are employed to detect changes in temperature, smoke concentration, hydrogen levels, and carbon monoxide concentrations within the energy storage station area prior to the occurrence of a fire.

2. Real-time monitoring of the air environment within the monitored area, with the equipment responding immediately to any changes in temperature or gas concentrations.

3. Employs CAN bus communication, offering convenient wiring and the ability to connect external functional devices.

4. Precisely monitor the gas within the energy storage compartment to eliminate false alarms and missed detections.

5. Three status indicator lights; the device features a self-test function that provides real-time feedback on its operational status.

 

Model

CN-TCQ02-HW

Operating voltage

DC24V

Types of Testing

Hydrogen, carbon monoxide, smoke detection, temperature detection, VOC (optional)

Detection Principle

Smoke detection: photoelectric sensor; Temperature detection: thermistor
Carbon monoxide: electrochemistry; hydrogen: semiconductor;

Gas sensor

Select imported or domestic brands based on service life and other factors.

Sensor lifespan

≥5 years

Hydrogen

Alarm setpoint: 190 × 10⁻⁶ (volume fraction)
Measurement range: (0~1000) × 10⁻⁶ (volume fraction)

Carbon monoxide

Alarm setpoint: 200 × 10⁻⁶ (volume fraction)
Measurement range: (0~1000) × 10⁻⁶ (volume fraction)

Temperature-sensing type

Category B

Addressing or not

Addressable, with CAN communication compatible with Zhongke microcontrollers.

Communication distance

Detector and controller: ≤1000 m

Operating current

10mA

Alarm Reset

Controller Reset/Power-Off Reset

Alarm Confirmation Light

LED display

Explosion-proof?

Yes, intrinsically safe

Explosion-proof marking

Ex ib llC T6 Gb

Explosion-proof Certificate Number

EETI24.0347X

Wiring system

Bus: CANL, CANH; DC 24V+, GND

Operating temperature

—10°C to +55°C (indoor); -40°C to +70°C (outdoor model)

Operating humidity

10% RH to 95% RH

Wind speed

Not greater than 8 m/s

External dimensions

91x65x27(mm)

Implementation Standard

GB 15322.1-2019 “Combustible Gas Detectors — Part 1: Point-Type Combustible Gas Detectors for Industrial and Commercial Applications”
GB 4715-2005 “Point-type Smoke Fire Detectors”
GB 4716-2005 “Point-Type Heat Fire Detectors”

 