Detailed Introduction

1. Capable of detector signal processing, initiating fire suppression device activation, and interlocking alarm functions, BMS Functions such as interlock communication serve as the data processing and communication hub for the electrochemical energy storage container fire suppression system;
2. Adopting a wall-mounted design, it features a compact footprint, powerful functionality, high reliability, flexible configuration, and convenient installation and operation.
3. Employs a Chinese-character LCD display and can print all system alarms and various operational messages in Chinese characters.

Brand | CAS and Micro |
Model | CN-KZQ100-HW |
CAN bus | CAN Bus Line 1: Three-in-One and Four-in-One Composite Detectors |
Two-wire bus | Bus No. 1: smoke detectors, heat detectors, manual call points, audible and visual alarms, modules, etc. |
485 communication interface | None |
Load-carrying capacity | CAN bus + fire alarm secondary bus = 192 units |
Rated power | ≤10W |
Output power | ≤62W |
Battery capacity | DC 12V 2.2Ah |
Control Output | Two-channel digital signal output |
Feedback Input | Two-channel digital signal input feedback |
Direct Start Button | Route 2 can be equipped with a direct-start button. |
Switch-mode power supply | 27V (±15%) 3A |
Operating temperature | —10℃ to +55℃ |
Operating humidity | ≤93%RH |
External dimensions | L 400mm × W 300mm × H 90mm |
Alarm Printing Interface | Thermal printer |
Display | 320×240 LCD dot-matrix display |