Committed to precision empowerment industry safety
Direct Fire Detection and Automatic Extinguishing System
Direct Fire Detection and Automatic Extinguishing System
Direct Fire Detection and Automatic Extinguishing System
+
  • Direct Fire Detection and Automatic Extinguishing System
  • Direct Fire Detection and Automatic Extinguishing System
  • Direct Fire Detection and Automatic Extinguishing System

Direct Fire Detection and Automatic Extinguishing System

The fire detection device is a pressure vessel filled with extinguishing agents. The detection pipes are arranged along potential fire hazard points. When the detection pipes are under pressure, they rely on their numerous detection points (linear) to detect open flames or temperature shocks. The detection pipe will burst at hot spots, causing a drop in pressure that triggers the valve to release the extinguishing agent and transmit a fire alarm signal.

Key words:

Direct Fire Detection and Automatic Extinguishing System

Service Hotline:

Case Details

  Working Principle

  The fire detection device is a pressure vessel filled with extinguishing agent. The fire detection tube is arranged along potential fire hazard points, and relies on its numerous detection points (linear) to detect when exposed to open flames or temperature shocks. The fire detection tube will burst at hot spots, causing the valve to actuate after the tube loses pressure, releasing the extinguishing agent and transmitting a fire signal.

  System Advantages

  The fire detection tube is made of a high molecular polymer, integrating flame retardancy, flexibility, and temperature sensitivity, capable of long-term leak resistance, with a maximum leakage rate of 10-5 mbar*l/s/m. It is a linear hose that is unaffected by dust, oil stains, and electromagnetic interference; the system operates independently without any external power supply and is not affected by power outages; the unique integrated valve design includes a ball valve to prevent damage and reduce the possibility of leakage; quick-connect fittings with dual sealing ring design ensure good sealing; high integration electromagnetic valve combination design provides customized solutions for customers, meeting the needs of different industries and application scenarios, with simple design and installation, and low maintenance costs.

  Technical Parameters of Fire Detection Tube

Inner Diameter Wall Thickness Density Actuation Temperature
4.0mm±0.04mm 1.0mm±0.1mm 1.05g/m3:±0.1 g/m3 170±10℃

  Product Model and Specifications

Type of Fire Detection Device Filling Amount of Extinguishing Agent Effective Protection Range Nominal Pressure (MPa) Maximum Working Pressure (MPa) Length of Fire Detection Tube (m) Length of Release Tube (m) Medium Selection
TH-Z-Q-3/2.5/170-FW 3Kg-5% 4.0m³ 2.5 4.2 20 / Heptafluoropropane
TH-Z-Q-6/2.5/170-FW 6Kg-5% 8.0m³ 2.5 4.2 20 / Heptafluoropropane
TH-Z-F-2/2.5/170-FW(1230) 2Kg-5% 2.2m³ 1.6 2.4 20 / Novec1230
TH-Z-F-3/2.5/170-FW(1230) 3Kg-5% 3.0m³ 2.5 3.2 20 / Novec1230
TH-Z-F-2/2.5/170-FW 2Kg-5% 2.2m³ 1.6 2.4 20 / Perfluorohexanone
TH-Z-F-3/2.5/170-FW 3Kg-5% 3.0m³ 2.5 3.2 20 / Perfluorohexanone

 

BAM

 

UL

 

VDS 

Application Scenarios


Project