Hydrogen, carbon monoxide, and smoke and temperature composite fire detection devices for energy storage power stations
Key words:
Hydrogen, carbon monoxide, and smoke and temperature composite fire detection devices for energy storage power stations
Classification:
Case Details

Product Introduction:
1. Uses high-sensitivity sensors to detect changes in temperature, smoke concentration, hydrogen, and carbon monoxide levels in the energy storage station area before a fire occurs.
2. Real-time monitoring of the air environment, with immediate response from the device when temperature and gas concentration changes are detected.
3. Utilizes CAN bus communication, with easy wiring and the ability to connect to other functional devices.
4. Accurately monitors gases in the energy storage cabin, eliminating false alarms and missed reports.
5. Three status indicator lights, the device has a self-check function to indicate its operational status.
Product Specifications:
Model
|
CN-TCQ02-HW
|
Operating Voltage
|
DC24V
|
Detection Types
|
Hydrogen, Carbon Monoxide, Smoke Detection, Temperature Detection, VOC (optional)
|
Detection Principle
|
Smoke Detection: Photoelectric Sensor; Temperature Detection: Thermistor |
Gas Sensor
|
Imported or domestic brands based on lifespan, etc.
|
Sensor Lifespan
|
≥5 years
|
Hydrogen
|
Alarm Set Value: 190*10-6 (volume fraction) |
Carbon Monoxide
|
Alarm Set Value: 200*10-6 (volume fraction) |
Temperature Detection Type
|
Class B
|
Addressable
|
Addressable, compatible with Zhongke and microcontroller CAN communication
|
Communication Distance
|
Detector to Controller: ≤1000m
|
Operating Current
|
10mA
|
Alarm Reset
|
Controller Reset/Power Reset
|
Alarm Confirmation Light
|
LED Display
|
Explosion-proof
|
Yes, Intrinsically Safe
|
Explosion-proof Mark
|
Ex ib llC T6 Gb
|
Explosion-proof Certificate Number
|
EETI24.0347X
|
Wiring System
|
Bus: CANL, CANH; DC24V+, GND
|
Operating Temperature
|
-10℃ ~ +55℃ (indoor); -40℃ ~ +70℃ (outdoor type)
|
Operating Humidity
|
10% RH~95% RH
|
Wind Speed
|
Not exceeding 8m/S
|
Dimensions
|
91x65x27(mm)
|
Standards Implemented
|
GB15322.1-2019 "Combustible Gas Detectors" Part 1: Point-type Combustible Gas Detectors for Industrial and Commercial Use" |
Product Certification:

Application Scenarios