Committed to precision empowerment industry safety
Hydrogen, carbon monoxide, and smoke and temperature composite fire detection devices for energy storage power stations
+
  • Hydrogen, carbon monoxide, and smoke and temperature composite fire detection devices for energy storage power stations

Hydrogen, carbon monoxide, and smoke and temperature composite fire detection devices for energy storage power stations

Key words:

Hydrogen, carbon monoxide, and smoke and temperature composite fire detection devices for energy storage power stations

Service Hotline:

Case Details

 

Product Introduction:

1. Uses high-sensitivity sensors to detect changes in temperature, smoke concentration, hydrogen, and carbon monoxide levels in the energy storage station area before a fire occurs.

2. Real-time monitoring of the air environment, with immediate response from the device when temperature and gas concentration changes are detected.

3. Utilizes CAN bus communication, with easy wiring and the ability to connect to other functional devices.

4. Accurately monitors gases in the energy storage cabin, eliminating false alarms and missed reports.

5. Three status indicator lights, the device has a self-check function to indicate its operational status.

 

Product Specifications:

Model

CN-TCQ02-HW

Operating Voltage

DC24V

Detection Types

Hydrogen, Carbon Monoxide, Smoke Detection, Temperature Detection, VOC (optional)

Detection Principle

Smoke Detection: Photoelectric Sensor; Temperature Detection: Thermistor
Carbon Monoxide: Electrochemical; Hydrogen: Semiconductor;

Gas Sensor

Imported or domestic brands based on lifespan, etc.

Sensor Lifespan

≥5 years

Hydrogen

Alarm Set Value: 190*10-6 (volume fraction)
Range: (0~1000)*10-6 (volume fraction)

Carbon Monoxide

Alarm Set Value: 200*10-6 (volume fraction) 
Range: (0~1000)*10-6 (volume fraction)

Temperature Detection Type

Class B

Addressable

Addressable, compatible with Zhongke and microcontroller CAN communication

Communication Distance

Detector to Controller: ≤1000m

Operating Current

10mA

Alarm Reset

Controller Reset/Power Reset

Alarm Confirmation Light

LED Display

Explosion-proof

Yes, Intrinsically Safe

Explosion-proof Mark

Ex ib llC T6 Gb

Explosion-proof Certificate Number

EETI24.0347X

Wiring System

Bus: CANL, CANH; DC24V+, GND

Operating Temperature

-10℃ ~ +55℃ (indoor); -40℃ ~ +70℃ (outdoor type)

Operating Humidity

10% RH~95% RH

Wind Speed

Not exceeding 8m/S

Dimensions

91x65x27(mm)

Standards Implemented

GB15322.1-2019 "Combustible Gas Detectors" Part 1: Point-type Combustible Gas Detectors for Industrial and Commercial Use"
GB4715-2005 "Point-type Smoke Fire Detectors"
 GB4716-2005 "Point-type Temperature Fire Detectors"

 

Product Certification:

Application Scenarios


Project